Commissioning
EL1502, EL1512
113
Version: 3.5
5.5.1.2
Operating mode selection
The EL1502 can be operated in four modes: The setting takes place by the
setting of single-channel operation or operation with two separate channels through the
selection of the
process data objects [
}
123]
+
Counter settings (up/down counter, gated counter)
in the CoE directory [
}
115]
.
The following operation modes are possible:
Opera-
tion
mode
Predefined PDO Assignment
Setting of the counting
direction via CoE directory
switchable outputs
1
(default)
1Ch. +/- Counter:
0x1A02 – CNT Inputs
+
0x1602 – CNT Outputs
Index 0x8020:05:
0: Enable UD counter
• UD input (terminal point 1):
sets the counting direction:
- High level: up;
- Low level: Down
• Clock input (terminal point 5):
indicates the individual pulses.
Output 1
2
Index 0x8020:05:
1: Enable pos. gate
• Gate is inhibited by a positive level
on the gate input (terminal point 1)
• Clock input (terminal point 5):
indicates the individual pulses.
+
Index 0x8020:04:
0: up counter
1: down counter
3
Index 0x8020:05:
2: Enable neg. gate
• Gate is inhibited by a negative level
on the gate input (terminal point 1)
• Clock input (terminal point 5):
indicates the individual pulses.
+
Index 0x8020:04:
0: up counter
1: down counter
4
2Ch. Counter
:
0x1A00 – CNT Inputs Channel 1
0x1A01 – CNT Inputs Channel 2
+
0x1600 – CNT Outputs Channel 1
0x1601 – CNT Outputs Channel 2
Index 0x8000:04 (Channel1) und
Index 0x8010:04 (Channel2)
0:up counter
1:down counter
Counter 1 → Output 1
Counter 2 → Output 2
In addition, the distributed clock function may be activated for the EL1502;
see below [
}
117]