Product description
EK1960
28
Version: 1.3.1
Test
Time until next test
Channel 1 (only channel 1 is tested)
b
Module switch (all four channels are tested)
b
Channel 2 (only channel 2 is tested)
b
Module switch (all four channels are tested)
b
Channel 3 (only channel 3 is tested)
b
Module switch (all four channels are tested)
b
Channel 4 (only channel 4 is tested)
b
Module switch (all four channels are tested)
b (next test channel 1)
NOTE
Length of the test pulses
When setting the test pulses, make sure that the connected actuator is not switched due to the test pulse
length.
The output signal must be 0 V for at least 200 µs within a test pulse. This is independent of the setting of
the parameter
MultiplierDiagTestPulse
.
Minimum load
The test pulse length of the outputs is set by default to 2 x 400 µs. This setting is suitable for typical
actuators with and without a protective circuit. The test pulse length can typically be reduced to 400
µs with a resistive load and a current of at least 30 mA.
Please observe the violation counter in the diagnostic history. If messages are displayed for the cor-
responding output module, this means that the setting of the test pulse length is borderline and may
need to be increased.
For electronic contactors that tend towards a capacitive behavior, it may be necessary to set the pa-
rameter
MultiplierDiagTestPulse
to 3 or higher.
Содержание EK1960 Series
Страница 1: ...Operating Instructions for EK1960 TwinSAFE Compact Controller 1 3 1 2019 01 28 Version Date...
Страница 2: ......
Страница 6: ...Table of contents EK1960 6 Version 1 3 1...
Страница 58: ...Operation EK1960 58 Version 1 3 1 Fig 51 Safety parameters of the input modules...
Страница 102: ...Operation EK1960 102 Version 1 3 1 Fig 131 Group Status Online ERROR Fig 132 Group Status Online STOP...
Страница 140: ...Appendix EK1960 140 Version 1 3 1 5 2 Certificates...