Operation
EK1960
133
Version: 1.3.1
4.20
Reaction times Bumper mode
If the operating mode BumperMode is set for inputs 8.7 to 8.10, safety mats or safety bumpers can be
evaluated at these inputs. The connection diagram can be found under
In this operation mode, the inputs give out a pulsed voltage. The pulse-pause-ratio and thus also the typical
response times are dependent on the internal cycle time of the EK1960.
Typical reaction times can be found in the following table. The given times indicate the reaction time from
switching the input to the response at the local output of the EK1960.
Cycle time EK1960
(value from 0xFEA0:09)
typical pulse-pause-ratio
(Switch On- / Switch Off time)
typical reaction time
1,1 - 2,5 ms
20 ms / 10 ms
9 ms - 31 ms
4,2 - 6,0 ms
50 ms / 30 ms
27 ms - 94 ms
7,2 - 9,0 ms
80 ms / 50 ms
40 ms - 139 ms
9,8 - 13,0 ms
100 ms / 70 ms
56 ms - 186 ms
13,4 - 19,5 ms
170 ms / 100 ms
86 ms - 292 ms
For a maximum possible configuration of the EK1960, a value of 350ms can be used as a worst case
estimate for the response time.
4.21
Reaction times ambient conditions
The TwinSAFE logic components check the environmental conditions, such as all internal and external
voltages and the temperature, within the logic cycle time. In the case of a maximum configuration on the
TwinSAFE logic, an error reaction can be expected typically after 10 seconds for over- or undervoltage, as
well as over- or under-temperatures.
4.22
Maintenance
The EK1960 TwinSAFE compact controller is maintenance-free!
WARNING
Observe the specified environmental conditions!
Make sure that the TwinSAFE compact controller is stored and operated only within the specified environ-
mental conditions (see Technical Data).
If the TwinSAFE compact controller is operated outside the permitted temperature range it will switch to the
Global Fault
).
4.22.1
Cleaning
Protect the TwinSAFE compact controller from impermissible soiling during operation and storage!
The TwinSAFE Compact Controller may not be operated any longer if it has been exposed to impermissible
soiling!
WARNING
Have dirty TwinSAFE compact controllers inspected!
The user is not permitted to clean the TwinSAFE controller!
Please send dirty TwinSAFE controllers to the manufacturer for inspection and cleaning!
Содержание EK1960 Series
Страница 1: ...Operating Instructions for EK1960 TwinSAFE Compact Controller 1 3 1 2019 01 28 Version Date...
Страница 2: ......
Страница 6: ...Table of contents EK1960 6 Version 1 3 1...
Страница 58: ...Operation EK1960 58 Version 1 3 1 Fig 51 Safety parameters of the input modules...
Страница 102: ...Operation EK1960 102 Version 1 3 1 Fig 131 Group Status Online ERROR Fig 132 Group Status Online STOP...
Страница 140: ...Appendix EK1960 140 Version 1 3 1 5 2 Certificates...