Operation
EK1960
97
Version: 1.3.1
Object „TSC Settings”
Depending on the terminal, the index designation of the configuration object „TSC Settings“ can
vary.
Example:
- EL3214-0090 and EL3314-0090, „TSC Settings“, Index 8040
- EL5021-0090, „TSC Settings“, Index 8010
- EL6224-0090, „TSC Settings“, Index 800F
Fig. 122: Entering the safety address and the CRC
TwinSAFE SC connections
If several TwinSAFE SC connections are used within a configuration, a different CRC must be se-
lected for each TwinSAFE SC connection.
4.11
Customizing / disabling TwinSAFE groups
The function Customizing
can be selected in the safety toolbars or via the TwinSAFE menu. It can be
used to enable and disable groups. There are different deactivation methods, as shown in the following
table.
Deactivation
Description
Permanent
deactivation
The TwinSAFE group is permanently disabled by the user. The substitute values
parameterized for the group are set for the group outputs.
If this group is enabled again, the RUN signal for this group must change from 0 to 1,
in order for the group to start.
Parameter:
Permanent Deactivation Allowed
: TRUE/FALSE
Deactivation until the
EL6910 is switched off
and back on again
The TwinSAFE group is disabled until the EL6910 is switched on again. The
substitute values parameterized for the group are set for the group outputs. This
setting cannot be used as default setting for the safety program download.
If this group is enabled again (other than by switching off and on again), the RUN
signal for this group must change from 0 to 1, in order for the group to start.
Parameter:
Temporary Deactivation Allowed
: TRUE/FALSE
Deactivation of
manual control unit
After starting the deactivation, the connection defined in the group must report a
COM error after a period of 10 seconds, for sample (default setting). If this is not the
case, a group error set and corresponding diagnostic message is generated. Only
one connection may be defined in the group, which must be a master connection.
Parameter:
Passification Allowed
: TRUE/FALSE
Timeout Passification Allowed
: Time in ms
Содержание EK1960 Series
Страница 1: ...Operating Instructions for EK1960 TwinSAFE Compact Controller 1 3 1 2019 01 28 Version Date...
Страница 2: ......
Страница 6: ...Table of contents EK1960 6 Version 1 3 1...
Страница 58: ...Operation EK1960 58 Version 1 3 1 Fig 51 Safety parameters of the input modules...
Страница 102: ...Operation EK1960 102 Version 1 3 1 Fig 131 Group Status Online ERROR Fig 132 Group Status Online STOP...
Страница 140: ...Appendix EK1960 140 Version 1 3 1 5 2 Certificates...