Operation
EK1960
74
Version: 1.3.1
Toolbar TwinCAT Safety
Icon
Name
Description
Verify Safety Project
The safety project is checked for validity.
Verify Complete Safety
Project
The safety project including the hardware level is checked for validity.
Download Safety Project
Loading the safety project onto the target system, here EL6910/
EJ6910
Delete Safety Project
Deleting the safety project from the target system, here EL6910/
EJ6910
Show Online Data of Safety
Project
Switching on the Online View for the safety project.
Customize Safety Project
Customizing the safety project (switching off TwinSAFE groups and
setting of safe substitute values for the group outputs). This is possible
if the online and offline CRC are the same and at least one group has
been configured for customizing.
Toolbar TwinCAT Safety CRC
Icon
Name
Description
CRC Toolbar Left-click on the toolbar to initiate an update of the CRCs by the user.
Red icon: CRCs are different
CRC Toolbar Green icon: All CRCs are identical
Online CRC CRC of the safety project on EL6910/EJ6910. This value is read online
by the EL6910/EJ6910. In the absence of an ADS connection to the
EL6910/EJ6910, this value is displayed with
.
Downloaded
CRC
CRC of the safety project that was loaded last. If no safety project is
loaded when the TwinCAT project is opened, the value is displayed
with
.
Offline CRC CRC of the current safety project, as stored in the safety editor. A CRC
is displayed, if the stored project is valid. If the project is invalid,
is displayed as CRC.
4.3.3.18
Checking the TwinSAFE addresses
The hardware addresses of the alias devices used can be checked and set via the dialog
Check Safe
Addresses
.
To this end, select the entry
Check Safe Addresses
via the node menu of the safety project node. A dialog
opens, which lists all alias devices that use hardware addresses. The addresses set in the software (
Safe/
FSoE Address
) and the hardware addresses (
Hardware Address
) are shown in separate columns for each
alias device and for the target system. In the column
Take Hardware Address
the user can specify whether
the hardware addresses for the alias devices settings are applied when the dialog is closed via the
OK
button.
Содержание EK1960 Series
Страница 1: ...Operating Instructions for EK1960 TwinSAFE Compact Controller 1 3 1 2019 01 28 Version Date...
Страница 2: ......
Страница 6: ...Table of contents EK1960 6 Version 1 3 1...
Страница 58: ...Operation EK1960 58 Version 1 3 1 Fig 51 Safety parameters of the input modules...
Страница 102: ...Operation EK1960 102 Version 1 3 1 Fig 131 Group Status Online ERROR Fig 132 Group Status Online STOP...
Страница 140: ...Appendix EK1960 140 Version 1 3 1 5 2 Certificates...