Product description
EK1960
17
Version: 1.3.1
plug
contact
Name
Description
Output (X9)
1
9.1
Output 17 from U
P5
(Channel5.FSOUT Module 5.Channel1.Output)
2
9.2
Output 18 from U
P5
(Channel5.FSOUT Module 5.Channel2.Output)
3
9.3
Output 19 from U
P5
(Channel5.FSOUT Module 5.Channel3.Output)
4
9.4
Output 20 from U
P5
(Channel5.FSOUT Module 5.Channel4.Output)
5
U
P5
Peripheral voltage U
P5
24 V
DC
(SELV/PELV)
6
9.5
Output 21 from U
P6
(Channel6.FSOUT Module 6.Channel1.Output)
7
9.6
Output 22 from U
P6
(Channel6.FSOUT Module 6.Channel2.Output)
8
9.7
Output 23 from U
P6
(Channel6.FSOUT Module 6.Channel3.Output)
9
9.8
Output 24 from U
P6
(Channel6.FSOUT Module 6.Channel4.Output)
10
U
P6
Peripheral voltage U
P6
24 V
DC
(SELV/PELV)
NOTE
Protected wiring
If the wiring of the outputs or the connected actuators leaves the control cabinet, the user must ensure that
the wiring is protected.
WARNING
Active loads
The use of active loads (with their own power supply) is not permissible unless the manufacturer of the load
ensures the non-reactivity of the power supply to the control signal.
DANGER
Clocked signals within a sheathed cable
Are clocked signals of different output modules used within a sheathed cable, a failure of a module, such as
cross-circuit or external power supply must lead to a switch off of all these modules. This switch off must be
performed by the user program.
From firmware version 03 and revision -0021 the parameter
Module Fault Link active
is available. If the pa-
rameter is set to TRUE for all modules involved, all these modules are set to the error state in the event of a
module error. This parameter is set to TRUE by default.
Содержание EK1960 Series
Страница 1: ...Operating Instructions for EK1960 TwinSAFE Compact Controller 1 3 1 2019 01 28 Version Date...
Страница 2: ......
Страница 6: ...Table of contents EK1960 6 Version 1 3 1...
Страница 58: ...Operation EK1960 58 Version 1 3 1 Fig 51 Safety parameters of the input modules...
Страница 102: ...Operation EK1960 102 Version 1 3 1 Fig 131 Group Status Online ERROR Fig 132 Group Status Online STOP...
Страница 140: ...Appendix EK1960 140 Version 1 3 1 5 2 Certificates...