Fig. 50: Safety parameters of the output and input modules
Overview of output parameters
PrmName
Index
Meaning
Value
FSOUT Module 0
Settings Common
8000:00 Settings for output module 0 (outputs 01 - 04)
-
ModuloDiag
TestPulse
8000:01 Test frequency of the clocking
All modules used are processed in succession in one logic cycle
respectively. With Modulo=0 the test is carried out in each cycle in
the respectively current module; with Modulo=1 only every second
pass and so on.
0
MultiplierDiag
TestPulse
8000:02 Duration of the clocking 1 = 400 µs (this value will need to be
increased according to the connected load if the outputs are open
circuit or in the case of very small output currents)
1
Standard Outputs
active
8000:03 FALSE = standard outputs deactivated
TRUE = standard outputs are ANDed with the safe outputs
FALSE
Diag TestPulse
active
8000:04 FALSE: Clocking of the outputs deactivated TRUE: Clocking of the
outputs activated
FALSE
Diag TestPulse for
Inputs active
8000:05 FALSE: Clocking of the outputs for local inputs deactivated
TRUE: Clocking of the outputs for local inputs activated. If TRUE is
set here the parameter DiagTestPulseActive is also set to TRUE.
FALSE
WARNING
Parameter
Diag TestPulse for Inputs active
If this parameter is activated, all outputs of this module are switched on and can be used as test pulses for
controller inputs. In this setting the parameter DiagTestPulseActive must be set to TRUE.
Corresponding parameters exist under the indices 8000:0 to 8050:0 for the output modules 0 to 5. The
module 8060:0 exists for the relay module.
The corresponding parameters are set for each input module on the Safety Parameter tab.
Содержание EK1960 Series
Страница 1: ...Operating Instructions for EK1960 TwinSAFE Compact Controller 1 3 1 2019 01 28 Version Date...
Страница 2: ......
Страница 6: ...Table of contents EK1960 6 Version 1 3 1...
Страница 58: ...Operation EK1960 58 Version 1 3 1 Fig 51 Safety parameters of the input modules...
Страница 102: ...Operation EK1960 102 Version 1 3 1 Fig 131 Group Status Online ERROR Fig 132 Group Status Online STOP...
Страница 140: ...Appendix EK1960 140 Version 1 3 1 5 2 Certificates...