6. Check the pressure in the installation. If the pressure is less than
1.5 bar, top up the water.
7. Open the valves on the connection plate.
8. Power the appliance back on.
9. Check the pressure in the installation. If the pressure is less than
1.5 bar, top up the water.
10. Activate the heating and check the flow rate in the installation. If the
flow rate is too low, clean the filter fully.
10.5.2 Full cleaning of the magnetic filter
If the flow rate in the installation is too low, fully clean the magnetic filter.
This operation requires the appliance to be fully drained.
1. Power off the appliance.
2. Isolate the appliance from the water supply.
3. Drain the appliance: connect a drain pipe to the filter nipple, then open
the valve on the filter tap by a quarter turn.
4. Once water stops running out of the pipe, close the valve on the filter.
5. Unscrew the sludge container using the handling tool provide in the
accessories bag.
Fig.77
MW-1001309-02
1.5
6
Fig.78
3
MW-1001310-1
Fig.79
4
MW-1001311-1
Fig.80
5
MW-1001312-1
10 Maintenance
7762758 - v05 - 19082020