Tab.75 Adv. Parameters menu
Parameter
Factory setting for each circuit
Description
ConfigZonePump
Out
(CP290
CP291
CP292
CP293
CP294 )
CIRCA1: Zone output
CIRCB1: Zone output
DHW1: DHW mode
CIRCC1: Zone output
CIRCAUX1: DHW looping
Configuration of Zone Pump Output
Zone output
CH mode
DHW mode
Cooling mode
Error report
Burning
Service flag
System error
DHW looping
Primary pump
Buffer pump
Zone Buffered
(CP770
CP771
CP772
CP773
CP774 )
CIRCA1: Yes
CIRCB1: Yes
DHW1: Yes
CIRCC1: Yes
CIRCAUX1: Yes
The zone is after a Buffer tank
No
Yes
9.4.4
Installation Setup > Air Src heat pump > Parameters,
counters, signals
HP : Heat-pump Parameters = Heat pump parameters
AP : Appliance Parameters = Appliance advanced parameters
Tab.76 Parameters menu
Parameter
Description
Factory setting
Bivalent temperature
(HP000)
Above the bivalent temperature, the backup energy source is not allowed to
operate
Can be set from -10 °C to 20 °C
5
Delay StartBackup
CH (HP030)
Start-up time delay for back-ups in central heating mode
Can be set from 0 Min 600 Min
0
Delay stop backup
CH (HP031)
Shutdown time delay for back-ups in central heating mode
Can be set from 0 Min to 600 Min
4
Delay Min.Outdoor
T. (HP047)
Start-up time delay for back-ups corresponding to the minimum outdoor tempera
ture HP049. The dynamic time delay is activated when HP030=0
Can be set from 0 Min to 60 Min
8
Delay Max.Outdoor
T (HP048)
Start-up time delay for back-ups corresponding to the maximum outdoor temper
ature HP050. The dynamic time delay is activated when HP030 = 0
Can be set from 0 Min 60 Min
30
Min.Outdoor
T.backup (HP049)
Minimum outdoor temperature used to set HP047.
Can be set from -30 °C to 0 °C
-10
Max.Outdoor
T.backup (HP050)
Maximum outdoor temperature used to set HP048.
Can be set from -30 °C to 20 °C
15
Min. Outdoor T. HP
(HP051)
Minimum outdoor temperature authorising heat pump operation.
Can be set from -20 °C to 5 °C
-20
Delay BackupStage
CH (HP108)
Time delay for activating the second electrical back-up stage in central heating
mode
Can be set from 1 Min to 255 Min
4
Min. water pressure
(AP006)
Appliance will report low water pressure below this value
Can be set from 0 bar to 6 bar
0.3
MessMinWaterPress
ure (AP058)
Warning message indicating that pressure is low
Can be set from 0 bar to 2 bar
0.8
9 Settings