Tab.86
Access
Parameter
Description
Value
23.5
Air Src Heat pump >
Parameters, counters, signals
> Parameters
Delay StartBackup CH
(HP030)
Delay time for starting the
backup energy source for the
heating circuits
Can be set from 1 to 600 mi
nutes.
If the Delay StartBackup CH
(HP030) parameter is set to 0,
the time delay for activating
the back-up is set depending
on the outdoor temperature.
20 minutes
Delay stop backup CH
(HP031)
Delay time for stopping the
backup energy source for the
heating circuits
4 minutes (default value)
If the Delay StartBackup CH parameter is set to 0, the time delay for
activating the back-up is set depending on the outdoor temperature: the
lower the outdoor temperature, the quicker the back-up will be activated.
t Time (minutes)
T Outdoor temperature (°C)
1 Delay Min.Outdoor T. (HP047)
2 Delay Max.Outdoor T (HP048)
3 Min.Outdoor T.backup (HP049)
4 Max.Outdoor T.backup (HP050)
Important
In this example, with the factory-set parameters, if the outdoor
temperature is 10 °C, the back-up will start up 25 minutes after the
outdoor unit of the heat pump.
Tab.87 Time delay curve parameters for tripping the back-up when Delay StartBackup CH (HP030) is set to 0.
Access
Parameter
Description
Value
23.5
Air Src Heat pump >
Parameters, counters, signals
> Parameters
Delay Min.Outdoor T.
(HP047)
Minimum duration of the time
delay for tripping the back-up
Can be set from 0 to 60 mi
nutes
8 minutes (default value)
Delay Max.Outdoor T
(HP048)
Maximum duration of the time
delay for tripping the back-up.
Can be set from 0 to 60 mi
nutes
30 minutes
Min.Outdoor T.backup
(HP049)
Minimum outdoor temperature
for the time delay for tripping
the back-up.
Can be set from -30 to 0 °C
-10 °C
Max.Outdoor T.backup
(HP050)
Maximum outdoor tempera
ture for the time delay for trip
ping the back-up.
Can be set from -30 to +20 °C
15 °C
Fig.71
MW-6000377-6
0
-10
-20
20
10
15
10’
20’
30’
t (min)
T (°C)
4
2
3
1
+10°C
25’
9 Settings
7762758 - v05 - 19082020
77