Tab.3
Outdoor unit conditions of use
Limit operating temperatures
AWHP 4.5 MR
AWHP 6 MR-3
AWHP 8 MR-2
Water in heating mode
+18 °C/+55 °C
+18 °C/+60 °C
+18 °C/+60 °C
Outdoor air in heating mode
-15 °C/+35 °C
-15 °C/+35 °C
-20 °C/+35 °C
Tab.4
Heating mode: outside air tempe7 °C, water temperature at the 35 °C. Performances in accordance
with EN 14511-2.
Measurement type
Unit
AWHP 4.5 MR
AWHP 6 MR-3
AWHP 8 MR-2
Heat output
kW
4.60
5.87
8.26
Coefficient of Performance (COP)
5.11
4.18
4.27
Absorbed electrical power
kWe
0.90
1.41
1.93
Nominal water flow rate (ΔT = 5 K)
m
3
/hour
0.80
1.04
1.47
Tab.5
Heating mode: outside air tempe2 °C, water temperature at the 35 °C. Performances in accordance
with EN 14511-2.
Measurement type
Unit
AWHP 4.5 MR
AWHP 6 MR-3
AWHP 8 MR-2
Heat output
kW
3.47
3.74
5.93
Coefficient of Performance (COP)
3.97
3.30
3.12
Absorbed electrical power
kWe
0.88
1.11
1.90
Tab.6
Common specifications
Measurement type
Unit
AWHP 4.5 MR
AWHP 6 MR-3
AWHP 8 MR-2
Total dynamic head at nominal flow rate
kPa
62
61.80
49.30
Nominal air flow rate
m
3
/h
2680
2700
3000
Power voltage of the outdoor unit
V
230
230
230
Start-up amperage
A
5
5
5
Maximal amperage
A
12
13
17
Acoustic power - Inside
dB(A)
43
43
51
dB(A)
58
65
65
Refrigerant fluid R410A
kg
1.4
1.3
3.2
R410A refrigerant
tCO
2
e
2.922
2.714
6.680
Refrigerant connection (Liquid - Gas)
inch
1/4 - 1/2
1/4 - 1/2
3/8 - 5/8
Max. pre-charged length
m
7
10
10
(1) Noise radiated by the envelope - Test run in accordance with the NF EN 12102 standard, temperature conditions: air 7 °C, water 55 °C
(2) Noise radiated by the envelope - Test run in accordance with the NF EN 12102 standard, temperature conditions: air 7 °C, water 45 °C
for AWHP 4.5 MR only (inner and outer sides).
(3) Quantity of refrigerant calculated in tonnes of CO
2
equivalent
Important
The quantity of refrigerant fluid in tonnes of CO
2
equivalent is
calculated using the following formula: quantity (in kg) of
refrigerant fluid x GWP / 1000. The Global Warming Potential
(GWP) of R410A is 2088.
3.2.3
Heat pump weight
Tab.7
Indoor module
Indoor module
Unit
Assure AWHP-IDU 4–8 E
Net weight
kg
59
Gross weight
kg
70
3 Technical specifications
12
7762758 - v05 - 19082020