Tab.74 Parameters menu
Parameter
Factory setting for each circuit
Description
MaxZoneTFlowS
etpoint
(CP000
CP001
CP002
CP003
CP004)
CIRCA1: Electrical back-up: 50
CIRCB1: Electrical back-up: 50
DHW1: Electrical back-up: 95
CIRCC1: Electrical back-up: 50
CIRCAUX1: Electrical back-up: 95
Maximum Flow Temperature setpoint zone
For circuit A: Can be set from 7 °C to 100 °C
Zone Function
(CP020
CP021
CP022
CP023
CP024)
CIRCA1: Direct
CIRCB1: Disable
DHW1: Disable
CIRCC1: Disable
CIRCAUX1: Disable
Functionality of the zone
Disable
Direct
Mixing Circuit
Swimming pool
High Temperature
Fan Convector
DHW tank
Electrical DHW
Time Program
ProcessHeat
DHW Layered
DHW Internal tank
DHW Commercial Tank
DHW FWS EXT
Zone HCZP
Comfort
(CP210
CP211
CP212
CP213
CP214)
CIRCA1: 15
CIRCB1: 15
DHW1: 15
CIRCC1: 15
CIRCAUX1: 15
Comfort footpoint of the temperature of heat curve of the circuit
Can be set from 15 °C to 90 °C
set to 15 = the curve base temperature is set automatically and is
the same as the room set point temperature
Zone HCZP
Reduced
(CP220
CP221
CP222
CP223
CP224)
CIRCA1: 15
CIRCB1: 15
DHW1: 15
CIRCC1: 15
CIRCAUX1: 15
Reduced footpoint of the temperature of heat curve of the circuit
can be set from 6 to 90 °C
set to 15 = the curve base temperature is set automatically and is
the same as the room set point temperature
TypeReducedNig
htMode
(CP340
CP341
CP342
CP343
CP344)
CIRCA1: Stop heat demand
CIRCB1: Stop heat demand
DHW1: Stop heat demand
CIRCC1: Stop heat demand
CIRCAUX1: Stop heat demand
Type of reduced night mode, stop or maintain heating of circuit
Stop heat demand
Continue heat demand
Control strategy
(CP780
CP781
CP782
CP783
CP784)
CIRCA1: Automatic
CIRCB1: Automatic
DHW1: not used
CIRCC1: Automatic
CIRCAUX1: Automatic
Selection of the control strategy for the zone
Automatic
Room Temp. based
Outdoor Temp. based
Outdoor & room based
9 Settings