1. Adjust the following domestic hot water production setting parameters:
Tab.47
Access
Parameter
Description
Adjustment required
DHW tank >
Parameters, counters,
signals > Parameters
Hysteresis DHW
(DP120)
Hysteresis temperature
relative to the DHW
temperature setpoint
Increase the set point tem
perature differential trigger
ing the domestic hot water
tank to be charged
Min. CH before DHW
(DP048)
Minimum heating duration
between two periods of
domestic hot water
production
Increase the minimum heat
ing duration between two do
mestic hot water production
runs
2. If possible, set the production of domestic hot water for overnight
periods using the timer programming for the domestic hot water tank.
9.2.6
Improving domestic hot water comfort
The system does not allow the simultaneous production of heating and
domestic hot water.
If the domestic hot water causes any kind of discomfort, the following
settings can be adjusted to improve the comfort level:
Modify the timer programming for domestic hot water production.
Schedule domestic hot water production based on your usage habits.
Modify the domestic hot water production setting parameters. The
consumption of electricity may rise.
1. Adjust the following domestic hot water production setting parameters:
Tab.48
Access
Parameter
Description
Adjustment required
DHW tank >
Parameters, counters,
signals > Parameters
Hysteresis DHW
(DP120)
Hysteresis temperature
relative to the DHW
temperature setpoint
Reduce the set point temper
ature differential triggering
the domestic hot water tank
to be charged.
Min. CH before DHW
(DP048)
Minimum heating duration
between two periods of
domestic hot water
production
Reduce the minimum heating
duration between two do
mestic hot water production
runs
Max. DHW duration
(DP047)
Maximum duration of the
domestic hot water
production
Increase the maximum au
thorised duration for domes
tic hot water production
DHW management
(DP051)
ECO mode: use of the heat
pump only. Comfort mode:
use of the heat pump and
backup energy sources
Select Comfort (HP+Boiler)
to systematically use the
heat pump and the back-ups.
9.2.7
Drying screed with an outdoor unit connected
The screed drying function reduces the drying time of the screed for
underfloor heating. This function must be activated for each zone.
Every day at midnight, the setpoint temperature is recalculated and the
number of days is decreased.
For the screed drying times, follow the screed manufacturer's
specifications.
On
On
9 Settings
60