1. Respect distances A, B and C between the outdoor unit 1 and the
indoor module 2.
Tab.20
A: Maximum/
minimum length
B: Maximum
height differ
ence
C: Maximum
number of el
bows
AWHP 4.5 MR 2 to 30 m
30 m
10
AWHP 6 MR-3 2 to 40 m
30 m
15
AWHP 8 MR-2 2 to 40 m
30 m
15
2. Make one or two horizontal loops with the refrigerant connections to
reduce disruption.
If the length of the refrigerant connections is less than 2 m, disruptions
can occur:
Functional disruptions caused by a fluid overload,
Noise pollution caused by the circulation of the refrigerant.
6.4
Positioning the indoor unit
6.4.1
Allowing sufficient space for the indoor module
Allow sufficient space around the heat pump indoor module to ensure
adequate access and facilitate maintenance.