Tab.81 Parameters
Parameter
Description
Factory setting
SCB-10
Digital input config
(EP046)
Sets the general configuration of the digital input
Stop h DHW
Stop heating
Stop DHW
Forced setpoint
Buffer Tank input
Stop h DHW
Logic level Digi In
(EP056)
Sets the logic level contact of the Smart Control Board digital input
Open
Closed
Off
Closed
Req FlowSetp digi In
(EP066)
Requested flow setpoint when digital input is configured to forced heat
Can be set from 7 °C to 100 °C
80
9.4.8
Installation Setup > Analogue input > Parameters,
counters, signals
EP : Entry Parameters = Input parameters
Tab.82 Adv. Parameters
ADV parameter
Description of the ADV advanced parameters
Factory setting
SCB-10
Sensor input config
(EP036)
Sets the general configuration of the sensor input Tsyst1
Disabled
DHW tank
DHW tank top
Buffer tank sensor
Buffer Tank top
System (cascade)
Disabled
Sensor input config
(EP037)
Sets the general configuration of the sensor input Tsyst2
Disabled
DHW tank
DHW tank top
Buffer tank sensor
Buffer Tank top
System (cascade)
Disabled
9.4.9
Installation Setup > 0-10 V input > Parameters, counters,
signals
Tab.83 EP : Entry Parameters = Input parameters
Parameter
Description
Factory setting
SCB-10
SCB func. 10V
PWMin (EP014)
Smart Control Board function 10 Volt PWM input
Off
Temperature control
Power control
Off
Max Setp Temp
0-10V (EP030)
Sets the minimum set point temperature for 0 - 10 volts for the Smart Control
Board
Can be set from 0 °C to 100 °C
0
Min Setp Power
0-10V (EP031)
Sets the maximum set point temperature for 0 - 10 volts for the Smart Control
Board
Can be set from 0.5 °C to 100 °C
100
9 Settings
7762758 - v05 - 19082020
75