13.3 Flame supervision and spillage monitoring system.
This pilot unit includes a system that will automatically shut off the gas supply if the
pilot flame goes out or if there is insufficient oxygen due to spillage or poor ventilation.
Check that the system operates properly as follows: -
!
Light the appliance. Set at the “HIGH” position and leave for one minute.
!
Turn back to “OFF” to extinguish the pilot.
Note the time when the pilot goes out
.
Listen for a snap sound at the gas tap.
Note the time when the sound is heard
.
This
sound is caused by an electromagnetic valve shutting off the gas supply through the tap.
The valve is located in the body of the tap. The valve should operate
within 60 seconds
of the pilot going out
.
If the valve does not operate within this time limit do not allow
the appliance to be used until the fault has been corrected.
This monitoring system must not be adjusted, bypassed or put out of operation.
This monitoring system or any of its parts must only be exchanged using Baxi Fires
Division authorised parts.
14. FASCIA INSTALLATION
14.1 Fitting the Eclipse fascia.
1.
Remove any protective film from the fascia.
2.
Carefully lift the fascia. Place the fascia against the
fireplace front surface so that the four retaining plates at
the back of the fascia are directly above the four
retaining brackets of the hotbox. There are two at the top
of the hotbox and two to the side of the burner module.
Lower the fascia unit making sure that the retaining
plates locate fully into the brackets on the hotbox (See
figure 27).
Page 30
INSTALLER GUIDE
©
Baxi Heating U.K. Limited 2007.
Figure 28. Identifying decorative trims
Figure 27. Fascia location
(Shown with Aspect fascia)