![B&R 8I84T200037.01P-1 Скачать руководство пользователя страница 343](http://html1.mh-extra.com/html/bandr/8i84t200037-01p-1/8i84t200037-01p-1_user-manual_460473343.webp)
Integrated safety functions
ACOPOSinverter P84 User's Manual 2.10
343
Warning!
CONTROL FAILURE
•
The designer of any wiring scheme must consider the potential failure modes of control chan-
nels and, for certain critical functions, provide a means to achieve a safe state during and af-
ter a channel failure. Examples of critical control functions include an emergency stop switch
(emergency stop) and overshoot stop.
•
Separate or redundant control channels must be provided for critical control functions.
•
Each implementation of a control system must be checked carefully and individually to ensure
faultless operation before the device is put into operation.
•
System control channels may include communication links. For this reason, the effects of un-
expected transmission delays and connection disruptions must be taken into account.
1)
Failure to follow these instructions can result in equipment damage, serious injury or death!
Caution!
INCOMPATIBLE MAINS VOLTAGE
Before switching on and configuring the frequency inverter, ensure that the mains voltage is compat-
ible with the supply voltage shown on the frequency inverter nameplate. The frequency inverter may
be damaged if the mains voltage is not compatible.
Failure to follow these instructions can result in equipment damage or injury.
Caution!
RISK OF LOSS OF POWER DUE TO CAPACITOR WEAR
The performance of product-specific capacitors may be reduced after long-term storage of over 2
years.
In this case, the following measures must be undertaken before using this product:
•
Use a variable AC power supply that is connected between L1 and L2 (also for model numbers
8I74T40xxxx.01P-1).
•
Increase AC supply voltage to the following values:
– 25% of the rated voltage for 30 minutes
– 50% of the rated voltage for 30 minutes
– 75% of the rated voltage for 30 minutes
– 100% of the rated voltage for 30 minutes
Failure to observe these instructions can result in damage to the device.
3.1.2 Personnel qualifications and usage
Personnel qualifications
Only trained employees who have read and understood the contents of this manual and all relevant product doc-
umentation are permitted to work on and with this product. In addition, these persons must have received relevant
safety instructions in order to recognize and avoid potential sources of risk. This personnel must have received
a technical education, collected knowledge and experience from the field and be able to foresee and recognize
dangerous situations that may result from the use of this product, modifying its settings or from the mechanical,
electrical and electronic components used throughout the entire system where this product will be used.
All persons who work with or near this product must be well-versed in all standards, guidelines and accident
prevention guidelines relevant to their activities:
1)
For additional information, refer to NEMA ICS 1.1 (latest edition), "Safety Guidelines for the Application, Installation and Maintenance of Solid State Control"
and NEMA ICS 7.1 (latest edition), "Safety Standards for Construction and Guide for Selection, Installation and Operation of Adjustable-Speed Drive Sys-
tems."
Содержание 8I84T200037.01P-1
Страница 2: ......
Страница 384: ...Accessories 384 ACOPOSinverter P84 User s Manual 2 10 8I0FT180 300 1 A Nm lb in 8I0FT180 300 1 25 221 3...
Страница 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Страница 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Страница 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Страница 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Страница 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Страница 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...