Programming guidelines
260
ACOPOSinverter P84 User's Manual 2.10
[CURRENT LIMIT] (CLI-)
Code
Name/Description
Setting range
Factory settings
CLI-
[CURRENT LIMIT.]
LC2
[Current limit 2]
[No]
(nO)
nO
[No]
(nO)
: Function not active
LI1
[LI1]
(LI1)
-
.
-
.
-
.
[...]
(...)
: See the assignment conditions
In state 0 of the input or the assigned bit, the first current limiting is active.
In state 1 of the input or the assigned bit, the second current limiting is active.
CL2
[2nd current limit]
1)
0 to 1.65 In
2)
1.5 In
2)
Second current limiting This parameter can be activated if
[2nd current limit]
(LC2)
is not equal to
[No]
(nO)
.
The adjustment range is limited to 1.36 In if
[Switch frequency]
(SFr)
is under 2 kHz.
Note:
If the setting is less than 0.25 In, the inverter can remain in error mode
[output phase loss]
(OPF)
, if this has been enabled,
"THERM. MOTOR PROTECTION (tHt) and LOSS OF MOTOR PHASE (OPL)" on page 292
. If it is below the no-load current of the
motor, the limitation has no effect.
Caution!
Make sure that the motor is designed to this current, since these are susceptible to a demagnetization.
Failure to follow this instruction can result in equipment damage.
CLI
[CURRENT LIMIT.]
1)
0 to 1.65 In
2)
1.5 In
2)
First current limiting.
The adjustment range is limited to 1.36 In if
[Switch frequency]
(SFr)
is under 2 kHz.
Note:
If the setting is less than 0.25 In, the inverter can remain in error mode
[output phase loss]
(OPF)
, if this has been enabled,
"THERM. MOTOR PROTECTION (tHt) and LOSS OF MOTOR PHASE (OPL)" on page 292
. If it is below the no-load current of the
motor, the limitation has no effect.
Caution!
Make sure that the motor is designed to this current, since these are susceptible to a demagnetization.
Failure to follow this instruction can result in equipment damage.
1)
This parameter can also be accessed via the
[SETTINGS]
(SEt-)
menu.
2)
In is the same as the rated current specified in the installation instructions and on the nameplate of the inverter.
Parameter that can be modified during operation or when stopped.
Содержание 8I84T200037.01P-1
Страница 2: ......
Страница 384: ...Accessories 384 ACOPOSinverter P84 User s Manual 2 10 8I0FT180 300 1 A Nm lb in 8I0FT180 300 1 25 221 3...
Страница 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Страница 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Страница 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Страница 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Страница 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Страница 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...