Programming guidelines
ACOPOSinverter P84 User's Manual 2.10
209
[Auto DC injection] (AdC-)
Code
Name/Description
Setting range
Factory settings
AdC-
[Auto DC injection]
AdC
[Auto DC injection]
[Yes]
(YES)
Automatic current injection on stopping (at the end of the ramp)
nO
[No]
(nO)
: No activation.
YES
[YES]
(YES)
: Activation with adjustable duration
Ct
[permanent]
(Ct)
: Continuous activation at standstill.
Warning!
This function blocks the function
[Magnet Mot]
(FLU)
see "FLUXING BY LI (FLI-)" on page 217
). If
[Magnet Mot]
(FLU)
is set to
[permanent]
(FCt)
,
[Auto DC injection]
(AdC)
must be set to
[No]
(nO)
.
Note:
This parameter gives rise to the injection of current even if a run command has not been sent. It can be accessed with the frequency
inverter running.
SdC1
[Auto DC inj. level 1]
1)
0 to 1.2 In
2)
0.7 In
2)
Height of the DC connection at standstill
[Auto DC injection]
(AdC)
is not set to
[No]
(nO)
. For this parameter, the value 0 will be forced if
[Motor
control type]
(Ctt)
(
see "Drive parameters (Ctt)" on page 153
) =
[Sync. Motor.]
(SYn)
.
Caution!
Check that the motor will withstand this current without overheating.
Failure to follow this instruction can result in equipment damage.
tdC1
[Auto DC inj. time 1]
1)
0.1 to 30 s
0.5 s
Standstill injection time. The parameter can be activated if
[Auto DC injection]
(AdC)
is not set to
[No]
(nO)
.
If
[Typ Motor control]
(Ctt)
(
see "Drive parameters (Ctt)" on page 153
) is set to
[FVC]
(FUC)
or
[Sync. Motor]
(Syn)
, this time is the hold time
at zero speed.
SdC2
[Auto DC inj. level 2]
1)
0 to 1.2 In
2)
0.5 In
2)
2nd level of standstill DC injection current.
The parameter can be activated if
[Auto DC injection]
(AdC)
is not set to
[No]
(nO)
.
For this parameter, the value 0 will be forced if
[Motor control type]
(Ctt)
see "Drive parameters (Ctt)" on page 153
[Sync. Motor.]
(SYn)
.
Caution!
Check that the motor will withstand this current without overheating.
Failure to follow this instruction can result in equipment damage.
tdC2
[Auto DC inj. time 2]
1)
0 to 30 s
0 s
2nd standstill injection time.
The parameter can be activated if
[Auto DC injection]
(AdC)
is not set to
[Yes]
(YES)
.
AdC
SdC2
Function
YES
x
Ct
≠ 0
Ct
= 0
Movement command
Frequency
Note:
If
[Motor control type]
(Ctt)
is set to
[FVC]
(FUC)
:
[I DC-Auto braking 1]
(SdC1)
,
[I DC-Auto braking 2]
(SdC2)
and
[time aut. DC
brake2]
(tdC2)
cannot be activated. Only
[time aut. DC brake 1]
(tdC1)
can be activated. This is then a hold time at zero speed.
1)
This parameter can also be accessed via the
[SETTINGS]
(SEt-)
menu.
2)
In is the same as the rated current specified in the installation instructions and on the nameplate of the inverter.
Parameter that can be modified during operation or when stopped.
Содержание 8I84T200037.01P-1
Страница 2: ......
Страница 384: ...Accessories 384 ACOPOSinverter P84 User s Manual 2 10 8I0FT180 300 1 A Nm lb in 8I0FT180 300 1 25 221 3...
Страница 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Страница 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Страница 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Страница 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Страница 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Страница 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...