Programming guidelines
ACOPOSinverter P84 User's Manual 2.10
143
Configuration parameters (continued)
Code
Name/Description
Setting range
Factory settings
GPE
[P component ENA]
1 to 9999
250
see "Drive parameters (EnA - rAP)" on page 160
GIE
[I component ENA]
0 to 9999
100
see "Drive parameters (EnA - rAP)" on page 160
UFr
[IR compensation]
25 to 200%
100%
see "Drive parameters (U0 - F5)" on page 154
SLP
[Slip compensation]
0 to 300%
100%
see "Setting parameters (FLU - JGt)" on page 145
dCF
[Ramp divider]
0 to 10
4
see "STOP MODE (Stt-)" on page 206
IdC
[DC inject. level 1]
0.1 to 1.41 In
1)
0.64 In
1)
Level of DC injection braking current activated via logic input or selected as stop mode.
see "STOP MODE (Stt-)" on page 206
Caution!
Check that the motor will withstand this current without overheating.
Failure to follow this instruction can result in equipment damage.
tdI
[DC injection time 1]
0.1 to 30 s
0.5 s
see "STOP MODE (Stt-)" on page 206
Maximum duration of current injection
[Current DC brake 1]
(IdC)
. After this time has expired, the DC connection becomes
[DC current brake 2]
(IdC2)
.
IdC2
[DC inject. level 2]
0.1 In (2) to
[DC current brake 1]
(IdC)
0.5 In
1)
see "STOP MODE (Stt-)" on page 206
The braking current is activated by the logic input or as a stop mode is selected, once the time span
[DC injection time 1]
(tdI)
has expired.
Caution!
Check that the motor will withstand this current without overheating.
Failure to follow this instruction can result in equipment damage.
tdC
[DC injection time 2]
0.1 to 30 s
0.5 s
see "STOP MODE (Stt-)" on page 206
Maximum duration of the connection
[DC injection current 2]
(IdC2)
, if the activation is selected as stop mode.
1)
In is the same as the rated current specified in the installation instructions or on the nameplate of the inverter.
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can also be
accessed and adjusted from within the configuration menu for the corresponding function, their description is detailed in these menus, on
the pages indicated, to aid programming.
Содержание 8I84T200037.01P-1
Страница 2: ......
Страница 384: ...Accessories 384 ACOPOSinverter P84 User s Manual 2 10 8I0FT180 300 1 A Nm lb in 8I0FT180 300 1 25 221 3...
Страница 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Страница 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Страница 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Страница 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Страница 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Страница 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...