![B&R 8I84T200037.01P-1 Скачать руководство пользователя страница 183](http://html1.mh-extra.com/html/bandr/8i84t200037-01p-1/8i84t200037-01p-1_user-manual_460473183.webp)
Programming guidelines
ACOPOSinverter P84 User's Manual 2.10
183
Alarms can be classified into 1 to 3 groups with the following submenus. Each of these groups can be assigned a
relay or logic output to the distributed signals. These groups can also be retrieved on the graphic display terminal
(see menu
[SELECT DISPLAY TYPE]
) and via the menu
[MONITOR]
(SUP)
.
If one or more of the alarms in a group of selected alarms occur, this alarm group is enabled.
[ERROR ALARM GR. 1]
(A1C-)
,
[ERROR ALARM GR. 2]
(A2C-)
,
[ERROR ALARM GR. 3]
(A3C-)
Code
Name/Description
A1C-
[ALARM GRP1 DEFINITION]
A selection must be made from the following list:
PLA
[Al. LI6=PTC]
(PLA)
: Alarm PTC sensor LI6=PTC
P1A
[Alarm PTC1]
(P1A)
: Alarm PTC sensor 1
P2A
[Alarm PTC2]
(P2A)
: Alarm PTC sensor 2
EFA
[Al ext fault]
(EFA)
: Alarm external fault
USA
[Undervoltage]
(USA)
: Alarm for an undervoltage
AnA
[Al haul err.]
(AnA)
: Alarm for a hauling error
CtA
[Thresh. I err.]
(CtA)
: Current threshold value reached (
[current threshold]
(Ctd)
)
FtA
[Thresh. Freq. err.]
(FtA)
: Frequency threshold is reached (
[F.-Thresh. Mot]
(Ftd)
)
F2A
[Thresh. Freq. 2 err.]
(F2A)
: Threshold frequency reached
[Thresh. freq. 2]
(F2d)
)
SrA
[FRH err.]
(SrA)
: Frequency reference reached
tSA
[Th Status Motor err]
(tSA)
: Motor thermal state 1 reached
tS2
[Th Status Motor 2 err]
(tS2)
: Motor thermal state 2 reached
tS3
[Th Status Motor 3 err]
(tS3)
: Motor thermal state 3 reached
UPA
[Voral. UVF]
(UPA)
: Prevention of undervoltage
FLA
[HSP err.]
(FLA)
: High frequency attained
tHA
[Al. °C ATV]
(tHA)
: Drive overheating
bSA
[Al brake haul err]
(bSA)
: Alarm speed during braking
bCA
[AI Brcont]
(bCA)
: Alarm feedback brake contact
PEE
[PID error alarm]
(PEE)
: PID controller error alarm
PFA
[Al. PID feedb.]
(PFA)
: Alarm PID feedback
AP2
[AI2 Al. 4-20]
(AP2)
: Alarm 4-20 mA signal at AI2 input not available
SSA
[Limt T/I err]
(SSA)
: Alarm torque limiting
tAd
[Th FU err]
(tAd)
: Thermal state of the inverter is reached
tJA
[Alarm IGBT]
(tJA)
: Alarm IGBT
rtA
[Al. T. contr.]
(rtA)
: Alarm torque control
bOA
[AI. brake res.]
(bOA)
: Alarm temperature of the braking resistor
APA
[Al. Option]
(APA)
: Alarm generated by an option card
UrA
[Alarm USF cons.]
(UrA)
: Reserved
rSdA
[Rope spg al.]
(rSdA)
: Slack rope (see parameter
[Config. slack rope]
(rSd)
)
ttHA
[Alarm high torque]
(ttHA)
: Motor torque exceeds upper threshold
[Torque thd. high]
(ttH)
ttLA
[Alarm low torque]
(ttLA)
: Motor torque below lower threshold
[Torque thd. low]
(ttL)
dLdA
[Alarm load variation]
(dLdA)
: Detection of a load deviation (see
[DET. DELTA LOAD]
(dLd-)
).
Refer to the procedure for multiple selection
A2C-
[ALARM GRP2 DEFINITION]
Identical to
[ERROR ALARM GR. 1]
(A1C-)
A3C-
[ALARM GRP3 DEFINITION]
Identical to
[ERROR ALARM GR. 1]
(A1C-)
Содержание 8I84T200037.01P-1
Страница 2: ......
Страница 384: ...Accessories 384 ACOPOSinverter P84 User s Manual 2 10 8I0FT180 300 1 A Nm lb in 8I0FT180 300 1 25 221 3...
Страница 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Страница 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Страница 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Страница 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Страница 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Страница 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...