Programming guidelines
148
ACOPOSinverter P84 User's Manual 2.10
Code
Name/Description
Setting range
Factory settings
PEr
[PID error Alarm]
0 to 65535
1)
100
see "PID CONTROLLER (Pld-)" on page 239
Regulator error monitoring threshold.
PSr
[Speed input %]
1 to 100%
100%
see "PID CONTROLLER (Pld-)" on page 239
Multiplying coefficient for predictive speed input.
rP2
[Preset ref. PID 2]
1)
300
see "PRESET PID REF (PrI-)" on page 241
.
Preset PID reference
rP3
[Preset ref. PID 3]
1)
600
see "PRESET PID REF (PrI-)" on page 241
.
Preset PID reference
rP4
[Preset ref. PID 4]
1)
900
see "PRESET PID REF (PrI-)" on page 241
.
Preset PID reference
Ibr
[Brake locked rotor current]
0 to 1.32 In
2)
0
see "[BRAKE LOGIC CONTROL] (bLC-)" on page 223
Current threshold of the break release for ascending or forward movement.
Ird
[Brake release I Rev]
0 to 1.32 In
2)
0
see "[BRAKE LOGIC CONTROL] (bLC-)" on page 223
Brake release current threshold for descending or reverse movement.
brt
[Brake Release time]
0 to 5.00 s
0 s
see "[BRAKE LOGIC CONTROL] (bLC-)" on page 223
Brake release time delay.
bIr
[Brake release freq.]
[Auto]
(AUtO)
0 to 10 Hz
[Auto]
(AUtO)
see "[BRAKE LOGIC CONTROL] (bLC-)" on page 223
Threshold value of the brake drop rate (brake release).
bEn
[Brake engage freq.]
[Auto]
(AUtO)
0 to 10 Hz
[Auto]
(AUtO)
see "[BRAKE LOGIC CONTROL] (bLC-)" on page 223
Threshold of the braking torque frequency.
tbE
[Brake engage delay]
0 to 5 s
0 s
see "[BRAKE LOGIC CONTROL] (bLC-)" on page 223
Time delay before request to engage brake. To delay the engaging of the brake (only for horizontal stroke) if the brake is applied as soon as
the inverter is completely stopped.
1)
If there is no graphic display terminal, then on the four-digit display the values over 9999 are shown with one point after the thousands unit, for example,
15.65 for 15650.
2)
In is the same as the rated current specified in the installation instructions or on the nameplate of the inverter.
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can also be
accessed and adjusted from within the configuration menu for the corresponding function, their description is detailed in these menus, on
the pages indicated, to aid programming.
Содержание 8I84T200037.01P-1
Страница 2: ......
Страница 384: ...Accessories 384 ACOPOSinverter P84 User s Manual 2 10 8I0FT180 300 1 A Nm lb in 8I0FT180 300 1 25 221 3...
Страница 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Страница 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Страница 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Страница 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Страница 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Страница 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...