8 / 28
0006080844_201003
E
N
G
L
I
S
H
HYDRAULIC DIAGRAM FOR BURNERS OPERATING WITH HEAVY OIL (50°E AT 50°C) WITH AUXILIA-
RY HEATER
HYDRAULIC DIAGRAM TO THE BURNERS OPERATING WITH LIGHT OIL OR HEAVY OIL WITH MAX
NOMINAL VISCOSITY 5 °E AT 50 °C
N° 0
00
29
01
18
0
N° 0
00
29
01
19
0
1 - Main tank
2 - Filter
3 - Circulation pump
4 - By pass (normally closed)
5 - Pressure regulator adjustable from 0,2 to 1 bar
6 - Pressure gauge (0 ÷ 4 bar)
The combustible recovery and degasifier tanks (dia
-
meter ~ 150, height ~ 400) should be installed as
near as possible to the burner and should be about
0,5 m. higher with respect to the burner’s pump.
1
- Main tank
2
- Steam or hot water coil to heat oil
3
- Filter
4
- Circulation pump
5
- By pass (normally closed)
6
- Pressure regulator (from 0,5 to 2 bar)
7
- Pressure gauge (0 ÷ 4 bar)
Electric heating wires
The combustible recovery and degasifier tanks (diameter
~ 150, height ~ 400) should be installed as near as possi-
ble to the burner and should be about 0,5 m. higher with
respect to the burner’s pump.