![baltur GI 1000 DSPN-D Скачать руководство пользователя страница 13](http://html.mh-extra.com/html/baltur/gi-1000-dspn-d/gi-1000-dspn-d_instructions-for-use-manual_470388013.webp)
9 / 28
0006080844_201003
E
N
G
L
I
S
H
HYDRAULIC DIAGRAM TO THE BURNERS OPERATING WITH THICK HEAVY OIL
(50° E AT 50° C) WITH AUXILIARY HEATER
N° 0
00
29
01
20
0
The combustible recovery and degasifier tanks (diameter ~ 150, height ~ 400) should
be installed as near as possible to the burner and should be about 0,5 m. higher with
respect to the burner’s pump.
1
- Main tank
2
- Steam or hot water coil to heat oil
3
- Filter
4
- Circulating pump
5
- Steam or hot water coil to heat oil
6
- Auxiliary heater
7
- Resistance
8
- Thermometer
9 - Degasifier (Ø = 100 - H = 300)
10 - By pass (normally closed)
11 - Pressure regulator (from 0,5 to 2 bar)
12 - Pressure gauge (0 ÷ 4 bar)
Heating electric cable
DETAIL OF FUEL PRESSURE ADJUSTING VALVE
N° 0
00
29
31
38
0
1 - Valve body
2 - Adjusting screw support plug
3 - Adjusting screw tap
4 - Adjusting screw
5 - Spring centering bush
6 - Spring
7 - Drilled piston
8 - Pin
9 - Pin holding plug
10- Pressure gauge connection plug
Содержание GI 1000 DSPN-D
Страница 2: ......
Страница 4: ......
Страница 32: ......
Страница 59: ...59 68 0006080844_201003 ...
Страница 60: ...60 68 0006080844_201003 ...
Страница 61: ...61 68 0006080844_201003 ...
Страница 62: ...62 68 0006080844_201003 ...
Страница 63: ...63 68 0006080844_201003 ...
Страница 64: ...64 68 0006080844_201003 ...
Страница 66: ...66 68 0006080844_201003 CONNETTORE RAMPA PILOTA PILOT GAS TRAIN CONNECTOR CONECTOR RAMPA PILOTO ...