CONNECTING LANDING PANELS
1.
Read the manual of landing panels (LOP) in Appendix-3, AP-03.
2.
Landing panels are serially connected and must have a unique floor
number id to communicate.
3.
All LOPs are delivered as their floor numbers already saved.
4.
So, read their floor numbers on their pockets to find their floor.
5.
You can set the floor number of any LOP at any time by following
the instructions in LOP manual AP03-LANDING OPERATING PANEL
in Appendix.
6.
Fix LOPs to the walls at the landings regarding to the instructions in
AP-03.
7.
Connect XK-CAN1 to RBM board in device.
8.
Connect all landing panels to the cable of XK-CAN1
9.
If the pit board (RBPB and CIO) is not used in system, a termination
resistor must be installed at the end of the line.
CONNECTING LANDING DOORS
1.
Connect XK-KK socket to the device terminals to connect door
contacts.
2.
At each floor disconnect the dummy white terminal shown below
and connect these cables to the door contacts. LKK/A-B is the name
of this cable.
3.
Connect green-yellow cable to the metal chassis of the door.