Installation
3. Installation
The following system blocks are referred to in this document:
AutroSafe
Fire-Alarm
Panel
EAU-321
Serial
comm..
BSL-336
VDR-
converter
VDR
Autronica Interface equipment
3.1 Pre-Requisites for Installation of BSL-336
•
AutroSafe system software version 3.4.1 or later (earlier
versions of the system may function, but are not certified for
use with BSL-336 by Autronica Fire and Security)
•
AutroSafe Serial-Communication Board EAU-321 — port 1 or
2 (See section 3.4 and control the jumper setting in chapter
3.3.1)
3.2 Requirements
•
Service computer; to run software
•
BSL-336 software CD, contains AutroCom test software and
documentation
•
Relevant test cables; to connect service computer to BSL-
336.
o
XJA-029 (configuration)
o
XJA-037 (control of VDR data)
3.3 Standard Communication Parameters
The BSL-336 is delivered from the factory containing the following
communication parameters:
•
Port 0, to VDR: 38400 baud, 8 data bit, none parity, 1 stop bit
•
Port 1, to AutroSafe: 19200 baud, 8 data bit, none parity, 1
stop bit
•
Service port, to service PC: 115200 baud, 8 data bit, none
parity, 1 stop bit
Interfacing Voyage Data Recorder Systems, AutroSafe Interactive Fire-Alarm System, 116-P-BSL336/EE, RevA 2007-01-25,