Description
Interfacing Voyage Data Recorder Systems, AutroSafe Interactive Fire-Alarm System, 116-P-BSL336/EE, RevA 2007-01-25,
Autronica Fire and Security AS
Page 5
2.2 Specifications
Physical
Dimensions (mm)
114,5 x 120 x 45 (HxDxW)
Weight 250g
Mounting
TS-35 DIN-rail (internally or externally to AutroSafe
panels)
Interface
Ports
Two asynchronous ports
VDR-
communication
Port 0
38400 baud, 8, N, 1
RS-232/RS-422
AutroSafe
communication
Port 1
19200 baud, 8, N, 1
RS-232
Service computer
Service port
115200 baud, 8, N, 1
RS-232
Cable Terminals
Screw connection, maximum 2.5mm
2
cable
Interface Options
Port 0 (to VDR)
RS-422 (maximum length 1000m)
Port 1 (to EAU-
321)
RS-232 (maximum length 10m)
Power
Power Supply
(from AutroSafe)
18–32V DC
Current
Consumption
Typically 150–200mA @ 24V DC
Environmental
Operating
temperature
–10–+60°C
Storage
temperature
–25–+70°C
Relative humidity
(operating and
storage)
10–95%, RH (non-condensing)
Level of Protection IP-20
EMC Compliance
Emissions
EN 50081-2 (94)
Immunity
EN 50082-2 (95)