Log Strings
Interfacing Voyage Data Recorder Systems, AutroSafe Interactive Fire-Alarm System, 116-P-BSL336/EE, RevA 2007-01-25,
Autronica Fire and Security AS
Page 28
8.1.2.2 Overview of Unit Types (Division Indicator (1)) — Internal Software
Controllers, Representations
Controller unit type
Code Valid range
Point
pt
0x0-0xfc
Detection zone
dz
0x0-0xfc
Fire alarm device
fd
0x0-0xfc
Fire protection equipment
fp
0x0-0xfc
Alarm zone
az
0x0-0xfc
Loop
dl
0x0-0xfc
Basic loop
bc
0x0-0xfc
Computer
co
0x0-0xfc
Domain network
do
0x0-0xfc
Operator panel
op
0x0-0xfc
Power
pw
0x0-0xfc
Operation zone
oz
0x0-0xfc
Log
lc
0x0-0xfc
Router
rt
0x0-0xfc
8.1.2.3 Example VDR log
A detector reports smoke. The Fire-Alarm System activates alarm
bells and outputs:
$FRFIR,E,103000,FD,PT,000,007,A,V,Fire PreAlarm: TEST PT7 Name TEST DZ2 Name*1D
$FRFIR,E,103002,FD,PT,000,007,A,V,Fire Alarm : TEST PT7 Name TEST DZ2 Name*78
$FREVE,103002,DZ00002,Fire Alarm On: TEST DZ2 Name*0F
$FREVE,103002,AZ00003,Zone Evacuate: TEST AZ3 Name*6F
$FREVE,103002,FP00013,Outp On : TEST FPD Name*0C
$FREVE,103002,FP00006,Outp On : TEST FP6 Name*7A
$FREVE,103002,FP00003,Outp On : TEST FP3 Name*7A
The panel operator presses SILENCE:
$FREVE,103020,OZ00001,Oper Silence : TEST OZ1 Name*36
$FREVE,103020,DZ00002,Fire AlACK On: TEST DZ2 Name*38
$FREVE,103020,OZ00001,Oper Silence : TEST OZ1 Name*36
$FREVE,103020,AZ00003,Zone Silenced: TEST AZ3 Name*64
The panel operator presses RESET:
$FREVE,103025,OZ00001,Oper Reset Sy: TEST OZ1 Name*17
$FREVE,103031,AZ00003,Zone Off : TEST AZ3 Name*34
$FREVE,103031,FP00013,Outp Off : TEST FPD Name*42
$FREVE,103031,FP00006,Outp Off : TEST FP6 Name*34
$FREVE,103032,FP00003,Outp Off : TEST FP3 Name*37
$FREVE,103035,OZ00001,Oper Reset Sy: TEST OZ1 Name*16