Log Strings
Interfacing Voyage Data Recorder Systems, AutroSafe Interactive Fire-Alarm System, 116-P-BSL336/EE, RevA 2007-01-25,
Autronica Fire and Security AS
Page 31
Examples:
$FRDOR,E,233042,FD,FP,000,010,O,O,Door Open : TEST FPA Name*6B
$FRDOR,E,233042,FD,FP,000,010,O,O,Door Trans(NA: TEST FPA Name*22
$FRDOR,E,233042,FD,FP,000,010,C,O,Door Closd(NA: TEST FPA Name*23
$FRDOR,E,233042,FD,FP,000,010,O,C,Door Open (Ac: TEST FPA Name*4D
$FRDOR,E,233042,FD,FP,000,010,O,C,Door Trans(Ac: TEST FPA Name*03
$FRDOR,E,233042,FD,FP,000,010,C,C,Door Closed : TEST FPA Name*6D
Explanation of the Description Text:
Description text
Door position Activated by AutroSafe
Comment
Door Open :
Open
Not Activated
Door Trans(NA:
In transition
Not Activated
Door Closd(NA:
Closed Not
Activated
Door Open (Ac:
Open
Activated (ordered closed)
Door Trans(Ac:
In transition
Activated (ordered closed) Occurs after a long delay
Door Closed :
Closed
Activated (ordered closed)
Note:
An activated door that is still open after the configured delay is
reported as a technical alarm (fault); this fault is logged as type EVE
to the VDR, as AutroSafe doesn’t distinguish FPE (Fire-Protection
Equipment) type information in fault messages. Example:
Example:
$FREVE,232535,FP00010,Unit Fault : TEST FPA Name C;0; Door not closed*