Log Strings
Interfacing Voyage Data Recorder Systems, AutroSafe Interactive Fire-Alarm System, 116-P-BSL336/EE, RevA 2007-01-25,
Autronica Fire and Security AS
Page 30
8.1.4.2 Timing (Configurable in AutroSafe, per Door Unit)
A status change in a non-activated door is reported within 15
seconds.
A status change in an activated door is typically reported in 2 minutes.
The purpose of the delay is to allow personnel to pass through closed
fire doors without causing a fault message on the fire-alarm panel.
Please be aware of these delays if you are testing fire doors.
$FRDOR, a, hhmmss, aa, aa, xxx, xxx, a, a, c--c
Field
no
Data form
Field name
Definition
0 $FRDOR Header
1
a
Message type
E – Event
2
hhmmss
Event time
The time is based on the AutroSafe timestamp
of the event. For periodic status, the timestamp
is the original time of the event.
3
aa
System indicator
FD – Fire Door
(this is the only value used in this field, even if
the installation also monitors other types of
doors)
4
aa
Division indicator (1)
AutroSafe UnitId.Type:
"FP" – Fire Protection Equipment
5
xxx
Division indicator (2)
UnitId.Number (MSD)
6
xxx
Door number
UnitId.Number (LSD)
7
a
Door status
O – Open
C – Closed
8
a
Mode switch setting
O – Harbour mode (allowed open)
C –
Sea mode (ordered closed)
9
c--c
Message's description text
The text contains three parts:
"Door"
<status :>, see below
Unit text from AutroSafe config.