Log Strings
8. Log Strings
8.1 String Definition
The strings follow the standards IEC61162-1 and NMEA0183; some
general knowledge of these standards is assumed. BSL-336 uses
strings defined in
IEC PAS 61162-102 Extra requirements for the
Voyage Data Recorder, Pre-standard First edition 2003-12.
AutroSafe transmits the following basic strings to the VDR:
Interfacing Voyage Data Recorder Systems, AutroSafe Interactive Fire-Alarm System, 116-P-BSL336/EE, RevA 2007-01-25,
Autronica Fire and Security AS
Page 26
String
Meaning
Unused
Fields
Event Alive
5 Minutes
Status
120 Minutes
FIR,E Fire-alarm
event
<none> X
X
FIR,F Fire-alarm
fault
8 X
X
FIR,D Fire-alarm
disabled
8 X
X
DOR,E Fire-door
event
<none> X
X
EVE Operator
events,
General
faults,
Periodic
status
<none>
X
X
<none>
X
X
<none>
X
X
X
ALA System
fault
event
<none> X
X
8.1.1 Talker Identifier
All strings from the fire-detection system are prefixed by the talker
identifier that signifies the fire-detection system:
$
FR
FIR,E,112405,FD,PT,000,007,A,V,Fire PreAlarm: TEST PT7 Name TEST DZ2 Name*1D
identifies the string as originating from the fire-detection system.
FR
8.1.2 Equipment Indicators/numbers
The various sentences contain fields that describe “division indicator”
and “door/detector number”. These may contain fire zone, central
number, deck number, loop number etc.
The BSL-336 is a simple protocol converter that does not contain
topology information. It does not tell which loop each detector is
connected to. AutroSafe refers to the hardware using a unique UnitId,
namely a two-letter code followed by a sequence number.