BSL_336 Installation
4.3 AutroSafe Configuration
Create installation file by following the procedure outlined below.
Start AS Configuration Tool
Graphical view opens
File>Open…
Choose configuration file
(example: ThisSite.ac)
"Add Unit(s)" dialogue opens
Right-click the panel in which EAU-321 is installed
Choose "Add…"
"Add Unit(s)" dialogue closes; return to graphical view
Select "Autrocom Serial"
Click "Add"
Select AUTROCOM_SERIAL, Autrocom Serial
Edit properties list to reflect the following:
AutroComPassWord: Local password (9999)
Description: Enter if required
Local Mode Report: Report as communication fault
Serial port on card: Serial port used on EAU-321 for BSL-336 connectivity
Baud rate: 19200
AutroComType Serial: SERIAL_SLIDING_WINDOW
Name: Voyage Data Recorder
View>Operation Zones
Operation Zones dialogue opens
Connect Unit dialogue opens
Right-click topmost Operation Zone
Select "Connect…"
In left pane, select "Autrocom Serial"
In right pane, select "Serial Interface for VDR Unit"
Click "Connect"
Save file
Click "Open"
Interfacing Voyage Data Recorder Systems, AutroSafe Interactive Fire-Alarm System, 116-P-BSL336/EE, RevA 2007-01-25,
Autronica Fire and Security AS
Page 16