background image

1/2

Doc. version 1.0

 

Indoor Isolated Callpoint

 

Installation

The Indoor Isolated Callpoint is an addressable indoor manual callpoint.

The callpoint signals the condition of a switch contact that is operated by 
pressing on a deformable element. After activation the deformable element 
is not destroyed and the callpoint can be reset.

The unit features a short-circuit isolator and meets the requirements of 
EN54 Pt. 11 and EN54 Pt. 17.

Details of the Status LED and activation are on Page 2.

Item

Order Number

MCP - Isolator Indoor

4099-5210

Resettable element (pack of 1)

515.001.127

Back box

515.001.021

1

Connect an 801AP MX Service Tool or an 850EMT into the 
programming port, noting the orientation. Now program the unit with 
the ID defined in the site configuration.

2

Implement the mounting method, for example:
– Use the dedicated back box (order number above). Fix this to the 

wall as a surface mount.

– Use a standard back box with fixing holes at 60.3 spacing, such as a 

standard UK single gang back box (BS4662). The box must be at 
least 25 mm deep. This will probably be let into the wall as a flush 
mounting option.

3

Route the loop wiring through the back box.

4

Connect the loop wiring to the push-fit connector as shown.

5

Remove the callpoint sliding front plate and deformable element 
assembly. This is described in “To replace the deformable element” 
below.

6

Connect the push-fit connector

7

Fix the callpoint to the back box using screws through the now-exposed 
fixing holes.

8

Re-fit the front plate assembly. Slide it into position then push upwards 
until it clicks into place.

Status LED

Press here to

activate

Loop -

Programming

Port

Push-fit

Connector

Loop +

Loop +

Loop -

Отзывы: