Limit switching M0010
Set end pos.CLOSED? M0084
Set end pos. OPEN? M0085
Select main menu
1.
Set selector switch to position 0 (OFF).
2.
Press push button C and hold it down for approx. 3 seconds.
➥
Display goes to main menu and indicates:
▶ Display...
Select parameter
3.
Select parameter either:
→
click via the menu
to parameter, or
→
via direct display: press and enter ID
M0084
.
➥
Display indicates:
Set end pos.CLOSED?
CLOSED or OPEN
4.
Use
Up ▲ Down ▼
to select:
→
▶ Set end pos.CLOSED? M0084
→
▶ Set end pos. OPEN? M0085
➥
The black triangle
▶
indicates the current selection.
5.
Press
Ok
.
➥
The display indicates either:
-
Set end pos.CLOSED? CMD0009 →
continue with step 9
-
Set end pos. OPEN? CMD0010 →
continue with step 12
-
Specialist (4) →
continue with step 6
User login
6.
Use
Up ▲ Down ▼
to select user:
Information: Required user level:
Specialist (4)
or higher
➥
The symbols have the following meaning:
-
black triangle:
▶
= current setting
-
white triangle:
▷
= selection (not saved yet)
7.
Press
Ok
to confirm to selected user.
➥
Display indicates:
Password 0***
8.
Enter password (
→
enter password).
➥
The display indicates either:
-
Set end pos.CLOSED? CMD0009 →
continue with step 9
-
Set end pos. OPEN? CMD0010 →
continue with step 12
Set end position
CLOSED
CMD0009
9.
Set again end position CLOSED:
9.1 For large strokes: Set selector switch in position Local control (LOCAL)
and operate actuator in motor operation via push button
(CLOSE) in
direction of the end position.
Information: Stop actuator before reaching end of travel (press STOP
push button to avoid damage.
9.2 Engage manual operation.
9.3 Turn handwheel until valve is closed.
9.4 Turn handwheel by approximately half a turn (overrun) in the opposite
direction of end position.
9.5 Set selector switch to position 0 (OFF).
➥
Display indicates:
Set end pos.CLOSED? Yes No
65
SAVEx 07.2 – SAVEx 16.2 / SARVEx 07.2 – SARVEx 16.2 Control unit: electronic (MWG)
ACVExC 01.2 Non-Intrusive Modbus RTU
Commissioning (basic settings)