Table 9:
Protection on site
Fuse
2)
3-phase AC motor 380 V – 480 V/50 Hz – 60 Hz
1)
Multi-turn
actuator
Blow characteristics:
Time-delay (gG)
[A]
Max. current
I
max
[A]
Rated current
I
N
[A]
Consumed rated
power
P
IN
[kW]
Type
6
1.8
1.3
0.6
SAVEx 07.2
SARVEx 07.2
6
2.5
1.3
0.6
6
3.5
1.5
0.7
6
2.8
2.0
0.9
SAVEx 07.6
SARVEx 07.6
6
4.3
2.3
1.1
6
4.8
2.7
1.2
6
4.4
2.8
1.3
SAVEx 10.2
SARVEx 10.2
10
6.9
3.6
1.6
10
7.4
4.0
1.8
10
6.1
3.8
1.7
SAVEx 14.2
SARVEx 14.2
16
11.0
6.1
2.8
20
15.2
7.8
3.5
16
9.9
6.5
2.9
SAVEx 14.6
SARVEx 14.6
20
17.9
9.9
4.5
25
22.6
12.3
5.6
20
17.2
10.9
5.3
SAVEx 16.2
SARVEx 16.2
For motor with different current type/mains voltage/mains frequency (refer to motor name plate).
Select fuse referring to the Electrical data sheet.
1)
The actuators are suitable for use in current circuits with a maximum short-circuit 1-phase AC current
value of 5,000 A root-mean-square (R.M.S). The output data of the fuses to be provided on site
2)
must not exceed the following values: 32 A/600 V at a maximum mains short-circuit alternating
current of 5,000 A AC.
Consider the max. current (I
max
) (refer to motor name plate or electrical data sheet)
when selecting the circuit breaker.
We recommend refraining from using residual current devices (RCD). However, if
an RCD is used within the mains, the residual current device must be of type B. DC
current may be present within the PE conductor.
Implementation of overcurrent protection devices is not required. Actuator controls
are equipped with own protection mechanisms, adapted to the actuator system.
Therefore, we recommend refraining from using overcurrent protection devices.
For actuator controls equipped with a heating system and external electronics power
supply, the fuses for the heating system have to be provided by the customer (refer
to wiring diagram F4 ext.)
Table 10:
Fuse for heating system
Designation in wiring diagram = F4 ext.
230 V AC
115 V AC
External power supply
1 A T
2 A T
Fuse
If actuator controls are mounted separately from actuator ( actuator controls on wall
bracket): Consider length and cross section of connecting cable when defining the
protection required.
Information
Separate mounting (actuator controls on wall bracket) requires prior consent of
AUMA.
25
SAVEx 07.2 – SAVEx 16.2 / SARVEx 07.2 – SARVEx 16.2 Control unit: electronic (MWG)
ACVExC 01.2 Non-Intrusive Modbus RTU
Electrical connection