4.5.1.
Mounting positions: modify
Flameproof enclosure, danger of explosion!
Risk of death or serious injury.
→
Before opening, ensure that there is no explosive gas and no voltage.
→
Wait for 30 seconds after power cut-off prior to opening the housing.
→
Handle cover and housing parts with care.
→
Joint surfaces must not be damaged or soiled in any way.
→
Do not jam cover during fitting.
Electrostatic discharge ESD!
Risk of damage to electronic components.
→
Earth both operators and devices.
1.
Loosen screws and remove the local controls.
2.
Check whether O-ring is in good condition, correctly insert O-ring.
3.
Turn local controls into new position and re-place.
Cable damage due to twisting or pinching!
Risk of functional failures.
→
Turn local controls by a maximum of 180°.
→
Carefully assemble local controls to avoid pinching the cables.
4.
Fasten screws evenly crosswise.
23
SAVEx 07.2 – SAVEx 16.2 / SARVEx 07.2 – SARVEx 16.2 Control unit: electronic (MWG)
ACVExC 01.2 Non-Intrusive Modbus RTU
Assembly