13.
Technical data
Information
The following tables include standard and optional features. For detailed information
on the customer-specific version, refer to the order-related data sheet. The technical
data sheet can be downloaded from the Internet in both German and English at ht-
tp://www.auma.com (please state the order number).
13.1.
Technical data Multi-turn actuators
Features and functions
Refer to name plate
Explosion protection
Certificates are attached to the device. All standards applied and their respective issues are indicated
on these certificates.
Certificates and standards
The particular conditions of use are listed on the certificates supplied.
Particular conditions of use
Short-time duty S2 - 15 min, classes A and B according to EN 15714-2
Standard:
Type of duty
(Multi-turn actuators for open-close
duty)
Short-time duty S2 - 30 min, classes A and B according to EN 15714-2
Option:
For 100 % nominal voltage and +40 °C ambient temperature and at run torque load at maximum output
speed.
Intermittent duty S4 - 25 %, class C according to EN 15714-2
Standard:
Type of duty
(Multi-turn actuators for modulating
duty)
Intermittent duty S4 - 50 %, class C according to EN 15714-2
Option:
For 100 % nominal voltage and +40 °C ambient temperature and at modulating torque load.
3-phase AC asynchronous motor, type IM B9 according to IEC 60034-7, IC410 cooling procedure ac-
cording to IEC 60034-6
Motors
Refer to name plate of ACV actuator controls
Permissible variation of mains voltage:
±
10 %
Permissible variation of mains frequency:
±
5 %
Mains voltage, mains frequency
Category III according to IEC 60364-4-443
Overvoltage category
F, tropicalized
Standard:
Insulation class
H, tropicalized
Option:
PTC thermistors (according to DIN 44082)
Standard:
Motor protection
Self-locking: Speed ranges 6 – 60 rpm and 12 – 108 rpm
NOT self-locking: Speed range variant 24 – 216 rpm
Self-locking
Multi-turn actuators are self-locking if the valve position cannot be changed from standstill while torque
acts upon the output drive.
110 – 120 V AC, 220 – 240 V AC or 380 – 480 V AC
Voltages:
Motor heater (option)
Power depending on the size 12.5 – 25 W
Manual drive for setting and emergency operation, handwheel does not rotate during electrical operation.
Manual operation
Handwheel lockable
Handwheel stem extension
Power tool for emergency operation with square 30 mm or 50 mm
Option:
Indication whether manual operation is active/not active via single switch (1 change-over contact)
Indication for manual operation (op-
tion)
AUMA Ex plug/socket connector with screw-type terminals (KP)
Standard:
Electrical connection
Ex plug/socket connector with terminal blocks (KES), increased safety Ex e
Ex plug/socket connector with terminal blocks (KES), flameproof enclosure Ex d
Ex plug/socket connector KT/KM, increased safety Ex e
Ex plug/socket connector KT/KM, flameproof enclosure Ex d
Option:
Metric threads
Standard:
Threads for cable entries
Pg-threads, NPT-threads, G-threads
Option:
Terminal plan according to order number enclosed with delivery
Terminal plan
88
SAVEx 07.2 – SAVEx 16.2 / SARVEx 07.2 – SARVEx 16.2 Control unit: electronic (MWG)
Technical data
ACVExC 01.2 Non-Intrusive Modbus RTU