figure 16 - Minimum clearances for the installation
around the Hydraulic module
300 mm
1000mm
500mm
minimum
150 mm*
*If the refrigerating connections need to be passed
behind the appliance.
A
B
2 .5 .2 Fitting the outdoor unit
The outdoor unit must be raised by at least 50 mm
from the ground. In snowy regions, this height must be
increased but must not exceed 1.5 m.
-
Attach the outdoor unit using screw and spring or split
washers to ensure they do not come loose.
2 .5 .3 Connecting the condensates drain
If an evacuation pipe must be used:
-
Use the elbow provided (
C
) and connect a flexible
hose diameter 16 mm to drain off the condensates.
-
Use the Plug(s) provided (
B
) to block the condensate
tray orifice.
Fit so that gravity flow of the condensates is ensured
(waste water, rainwater, gravel bed).
"
If it is installed in a region where the temperature
can drop below 0 °C for long periods, fit a
tracing resistor to the drain pipe to avoid it
freezing up . The resistance trace must heat not
just the evacuation pipe but also the bottom of
the condensate drip tray of the appliance .
2 .6 Installation of the Hydraulic module
2 .6 .1 Requirements to installation space
The room where the appliance operates must respect
the regulations in force.
The appliance must be installed in a suitable and well
ventilated room. The room must have a new air inlet (A)
figure 15 - Fit the outdoor unit,
evacuation of the condensates
* In regions where there is often snow,
(H) must be higher than the average thickness of snow.
B
B
C
Installation and operating manual
"
1605 - EN
"
alfea hybrid duo heat pump oil low NOx CH
- 16 -