figure 48 - Diagram of the floor slab drying programmes
50
45
40
35
30
20
5
0
25
55
1
1
5
7
X
10
18
25
15
1
initial temperature heating °C
Heating w heating ready for occupation
Heating ready for occupation
Day
Functional
heating
"
Respect the standards and reference values of the builder! Correct
operation of this function is only possible with a correct installation
(hydraulic, electricity and settings)! The function may be interrupted
earlier by setting to "Stop" .
Line
Function
Setting range or display
Setting increment
Basic setting
791
S
Max. optimisation when switching off
0 360 min
10 min
120 min
(anticipation of stoppage to switch from comfort to reduced)
800
S
Start increasing the reduced operation
-30... 10 °C
1 °C
--
801
S
End of increase in reduced operation
-30... 10 °C
1 °C
-5 °C
830
S
Raising of mixing valve
0... 50 °C
1 °C
0
834
S
Servomotor travel time
30... 873 s
1 s
240 s
850
I
Stop
-
Stop= early interruption of the current programme, programme inactive
-
Functional heating
-Curing heating
-
Functional h Curing heating
-Curing h functional heating
-Manual
The manual mode ca be used to programme the slab drying .
The function ends automatically after 25 days.
851
I
manual slab drying reference value
(if line 850 = manual)
0... 95 °C
1 °C
25 °C
This function allows the customised floor drying temperature to be set. This temperature remains fixed.
The floor drying programme stops automatically after 25 days of operation.
856
I
Current drying day
0 32
857
I
Drying days completed
0 32
900
S
Operating mode changeover
None, protection mode,
reduced, comfort, Automatic
1
Protection
mode
Operating mode at the end of floor drying.
Installation and operating manual
"
1605 - EN
"
- 43 -
alfea hybrid duo heat pump oil low NOx CH