Line
Function
Setting range or display
Setting increment
Basic setting
Setting the heating, circuit 2
If the installation is composed of 2 heating circuits (only displayed with 2nd circuit kit option)
1010
U
Ambient comfort temperature value
Reduced temperature …
max. comfort reference value .
0.5 °C
20 °C
1012
U
Reduced setpoint
frost protection temperature …
comfort temperature
0.5 °C
18 °C
1014
U
Frost protection setpoint
4 °C… reduced temperature
0.5 °C
8 °C
1016
S
Maximum comfort value
20... 35 °C
1 °C
28 °C
1020
I
slope of the heating curve (see
0 1 4
0 02
0.5
1021
I
Translation of the heating curve
-4.5... 4.5 °C
0.5 °C
0
1026
S
Translation of the heating curve
Stop, Start
Stop
Warning!
Do not modify, leave on Stop.
1030
I
Summer/winter heating limit
8... 30 °C
0.5 °C
18 °C
When the mean of the external temperatures over the last 24 hours reaches 18°C the regulator stops the heating (economy).
In summer operation, the display shows "Eco". This function is only active in automatic operation.
1032
S
Daily heating limit
-10... 10 °C
1 °C
-3 °C
This function permits, between seasons, to deviate partially from the automatic switching between summer/winter.
If the value is increased, the switch to summer operation is delayed.
If the value is reduced, the switch to summer operation is brought forward.
This function is only active in automatic operation.
1040
S
min. initial reference value . (for fan-
convector)
8... 95 °C
1 °C
8 °C
1041
S
Max. start value
8... 95 °C
1 °C
80 °C
Heated floor= 50 °C
Important remark
:
The maximum limit is not a safety function as that required for under-floor heating.
1050
S
Ambient influence
1 %... 100 %
1 %
20 %
If the installation is equipped with an ambient sensor:
This function allows the influence of the ambient temperature on the regulation to be chosen.
If no value is entered, the regulation is via the water logic.
If the parameter is set to 100%, the regulation is only made using the ambient temperature.
1090
S
Maximum optimisation when started
0 360 min
10 min
0
1091
S
Maximum optimisation when stopped
0 360 min
10 min
0
1100
S
Start increasing the reduced operation
-30... 10 °C, --°C
1 °C
--
1101
S
End of increase in reduced operation
-30... 10 °C, --°C
1 °C
-5 °C
1130
S
Raising of mixing valve
0... 50 °C
1 °C
0
1134
S
Servomotor travel time
30... 873 s
1 s
240 s
1150
I
Floor slab drying check (
Stop
-
Stop= early interruption of the current programme, programme inactive
-
Heating working.
-Heating ready for occupation
-
Heating w heating ready.
-
Heating ready for occu heating working
-
Manual - The manual mode ca be used to programme the slab drying .
The function ends automatically after 25 days.
1151
I
Floor slab drying reference value (if line1150 =
Manual)
0... 95 °C
1 °C
25 °C
This function allows the customised floor drying temperature to be set. This temperature remains fixed.
The floor drying programme stops automatically after 25 days of operation.
1156
I
Current drying day
0 32
1157
I
Drying days completed
0 32
Installation and operating manual
"
1605 - EN
"
alfea hybrid duo heat pump oil low NOx CH
- 44 -