14
© 2019, ATEÏS, member of PAX ProAV Group
Voltage mode: Trigger the input by a voltage change (OPEN/CLOSE) with an external
24VDC source provided by external devices. The cable is not monitored in this mode.
6. 24 VDC output:
Provide 24VDC (max. 1.3A) power for external devices. Please note the power is shared by the
two 24VDC outputs on BTQ-VM4/8 controller and the remote consoles.
7. Logic input:
There are eight logic inputs designed to work with simple contact or button, and the two states
input (open contact, close contact) can be specified to any of those logic input to monitor
security devices such as power supply, then those control inputs can put the system into a
security mode for power saving purpose.
8/9. Evac & Fault contacts output:
The Evac and Fault output contact will reflect the evacuation status and the general fault status
of the BOUTIQUE system.
8. EVAC contact: This contact is closed if the system is under EVAC paging.
9. Fault contact: This contact is open if a system or major fault is detected.
10. Remote console (RJ45):
The remote port(s) allows the paging consoles or accessories to be connected to BTQ-VM4/8/
SG/SL unit. Each remote port on BTQ-VM4/8 controller and BTQ-SL8/SG8 unit can address up
to 8 DPM-MAIN remote consoles in daisy-chain or up to 16 units in redundant loop using 2
ports.
Max. remotes per BTQ-SL8: 8
Max. remotes per BTQ-VM4/8: 16
Max. distance between digi-link remote units: 250m (shielded RJ45 connector, STP
CAT5/6).
11. USB 2.0 interface:
Connect a USB flash drive for external storage of music/message files and playback (G.711,
G.722, G.726, G.727, MP3 and WAV).
12. Digi-Link port (RJ45):
The local digi-link network is used to link the BTQ-VM4/8 controller and BTQ-SL8 secondary
units together.
Max. local-net units: 32
Max. distance between local-net units: 10m (shielded RJ45 connector, STP CAT5/6).
13. Ethernet connector (RJ45):
Connect the BTQ-VM4/VM8 controller to Ethernet network.
14. RS232:
This port is used to connect to 3rd party device for controlling the BOUTIQUE system.
15. 24VDC out:
Provide 24VDC (max. 1.3A) power for external devices. Please note the power is shared by the
two 24VDC outputs on BTQ-VM4/8 controller and the remote consoles.
16. Audio line output:
Connect an external device such as earphone, speaker or recording device etc. to listen and
monitor the audio during zone paging.
17. External amp In: