Configuration
113
© 2019, ATEÏS, member of PAX ProAV Group
o
Trigger: Start the event which selects from [ON Function] drop-down box. To stop the
event, trigger the
event which selects from [OFF function].
Stop type: Select a type to deactivate the Evac event/Alarm event.
o
Immediately: The Evac/alarm message playing on Evac event or Alarm event will be
stopped immediately.
o
End of single: The Evac/alarm message playing on Evac event or Alarm event will be
stopped after the current audio message ends.
o
End of round: The Evac/alarm message playing on Evac event or Alarm event will be
stopped after playing this round of the pre-chime, post-chime, and channel 0~channel 8.
Output contact:
o
Close to trigger: The [ON Function] event will be triggered when the evac input is close,
and open to trigger the [OFF Function] event.
o
Open to trigger: The [ON Function] event will be triggered when the evac input is open,
and close to trigger the [OFF Function] event.
Latch mode: Set the normal logic input to be in latch mode for this event when connecting to a
latching ON-OFF switch button, it requires to input state from Hi to Low to start the event, and
input state from Low to Hi to stop the event.
Mode: Monitor, Disable (contact without monitor) and Voltage.
1. Monitor: The cables which connect to evacuation input are monitored (4 status: open,
short, off, on).
2. Disable: The cables which connect to evacuation input will not be monitored (faults will
not be detected).
3. Voltage: Trigger the input by a voltage change with an external 24VDC source provided by
external devices. The Voltage mode is an alternative way of using contact. The cable is
not monitored in this mode.
ON/OFF function: Select the event which will be triggered by this Evac input.
Zone selection (Z1-Z8): Select zones of paging for Evacuation or Alarm event.
5.1.8.2.1.1 Edit evac/alarm event
Here you can configure the messages for Evac event and Alarm event. For example, when a building
is on fire, this Evac event/Alarm event will play a pre-chime, evac/alert message files
(channel0~channel8) and post-chime in order to help evacuation.