Manual Weighing Controller A 810
Page
106
A.S.T. Angewandte SYSTEM-TECHNIK GmbH Dresden
6.8. Sequence Mode with Adjust Feeding
Enable Adjust Feeding in “
AdFd
” (3.1.8.3 in submenu “SEQU”).
In Sequence Mode the Over / Under comparison is done when the Complete output is ON.
Timer “CFT” re-opens SP3 for a certain time to adjust final weight.
Timers:
t1: Comparison Inhibited Time “CITI” – set in 3.1.7.6 at page 42
t2: Judging Time “JTI” – set in 3.1.7.7 at page 42
t3: Complete Output Time ”COTI” – set in 3.1.7.8 at page 43
t4: Compensation Feeding Time “CFT” – set in 3.2.3.2.15 at page 71