16
Tensor
6.1
LED display module
The LED display module simplifies the setup of the actuator via a clear presentation of the
menu items in the double-digit 7-segment display.
6.2
Potentiometer (electronic via additional board)
Connection configuration
Use only shielded wires
18
GND Poti
19
Output Poti 0...100% (Wiper, output impedance 1 kΩ)
20
+Ub Poti 5...24 V DC
56, 57
Fault message output (potential free closer max. 200 V/0.5 A)
Actual value output of the potentiometer end position
The actual value has to be determined for both stop positions.
•
Choose menu item „PL“ for programming the left end position or „PR“ for the right end position and confirm with button
[M]. The Display indicates a confirmation dialogue.
PL
Pt
•
Set the desired value with [R] or [L]. The Display indicates a confirmation dialogue.
L_
.
0%
Lw
.
10%
Ln
.
90%
L_
.
100%
L
≡.
free values
•
Save the value with the button [M], this will activate the next menu item automatically.
The potentiometer module has to be evaluated in the voltage division circuit in general.
U+
U–
UM
18
19
20
5–24 V DC
max. 0,5 A
5–24 V
DC
57
56