Tensor
Ao
Modus
Function
Description
---
Manu
Off
Contact open
A0
Auto
Off
Contact open
A1
Auto
Fault & stall Error
Contact open in the event of a fault
A2
Auto
Fault & stall warning Contact open in the event of a fault
8.2.1.6 Message deviation Control
ad
Activate
•
Select menu item
ad
and confirm with button [M]
•
Select value 0…9 and confirm with button [M]
0 (message off)
1…9 (at deviation 1…9% between actual and set value a fault message is issued). Right and left end position as well as
parameterized right and left set value are the reference
•
Finally save new setting
Ad
0
Message off
1…9
At deviation 1..9% between actual and set value a fault message is issued
Example:
Menu status 2=2%
Right end position 0% [0°] / left end position 100% [90°]. At a distance of 90° corresponds a setting of 2% 1,8°. If the current
actual value deviates by more than 1,8° from the current set value default, the signal contact switches (opens).
8.2.1.7 Hysteresis run (motor start and stop)
Start and stop run of the engine can be influenced by a hysteresis function. e.g. to protect the mechanism and to increase the
reliability in operation.
H
.
b
Switch-off hysteresis
H
.
d
Switch-on hysteresis
With "Hb" (H-brake) the switch-off hysteresis of 0 - 80% is set. "Hd" (H-difference) defines a hysteresis between 0 - 90% for the
switch-on run. A value of 0% disables the hysteresis functions.
•
Select menu item „Hb“ or „Hd“ and open the sub menu with button [M].
•
Set a value between 0 and 80% (0...8) for Hb or 0 and 90% (0...9) for Hd. The difference of set value and actual value is
compared with the hysteresis. If this difference is less than the switch-off hysteresis, the drive stops. If its larger than the
switch-on hysteresis, the drive regulates.