The function generates general time stamped ON/OFF events to the common event buffer from each of
the two (2) output signals as well as several operational event signals. The time stamp resolution is 1
ms. The function also provides a resettable cumulative counter for OPEN, CLOSE, OPEN FAILED, and
CLOSE FAILED events.
The following figure presents a simplified function block diagram of the object control and monitoring
function.
Figure. 5.4.2 - 86. Simplified function block diagram of the object control and monitoring function.
Settings
The following parameters help the user to define the object. The operation of the function varies based
on these settings and the selected object type. The selected object type determines how much control
is needed and which setting parameters are required to meet those needs.
Table. 5.4.2 - 107. Object set and status.
Name
Range
Default
Description
Local/Remote
status
0: Local
1: Remote
1:
Remote
Displays the status of the relay's "local/remote" switch. Local controls cannot
override the open and close commands while device is in "Remote" status. The
remote controls cannot override the open and close commands while device is
in "Local" status.
OBJ LN mode
1: On
2: Blocked
3: Test
4: Test/Blocked
5: Off
1: On
Set mode of OBJ block.
This parameter is visible only when
Allow setting of individual LN mode is
enabled in
General menu.
OBJ LN
behaviour
1: On
2: Blocked
3: Test
4: Test/Blocked
5: Off
-
Displays the mode of OBJ block.
This parameter is visible only when
Allow setting of individual LN mode is
enabled in
General menu.
Object name
-
Objectx The user-set name of the object, at maximum 32 characters long.
Object type
0: Withdrawable
circuit breaker
1: Circuit
breaker
2: Disconnector
(MC)
3: Disconnector
(GND)
1:
Circuit
breaker
The selection of the object type. This selection defines the number of required
digital inputs for the monitored object. This affects the symbol displayed in
the HMI and the monitoring of the circuit breaker. It also affects whether the
withdrawable cart is in/out status is monitored. See the next table ("Object
types") for a more detailed look at which functionalities each of the object types
have.
A
AQ
Q-T256
-T256
Instruction manual
Version: 2.06
© Arcteq Relays Ltd
IM00028
181