Name
IEC
ANSI
Description
DR
-
-
Disturbance recorder
CBW
-
-
Circuit breaker wear monitor
THD
-
-
Total harmonic distortion
MR
-
-
Measurement recorder
VREC
-
-
Measurement value recorder
5.2 Measurements
5.2.1 Current measurement and scaling in differential applications
The current measurement module (CT module, or CTM) is used for measuring the currents from
current transformers. The measured values are processed into the measurement database and they
are used by measurement and protection functions. It is essential to understand the concept of current
measurements to be able to get correct measurements.
Figure. 5.2.1 - 2. Current measurement terminology
PPRI:
RI: The primary current, i.e. the current which flows in the primary circuit and through the primary side
of the current transformer.
SEC:
SEC: The secondary current, i.e. the current which the current transformer transforms according to its
ratios. This current is measured by the protection relay.