Table. 5.3.9 - 84. Register content.
Name
Description
Date and time
dd.mm.yyyy hh:mm:ss.mss
Event
Event name
Time to reach 100 % theta
seconds
Ref. T current
x I
n
Active meas. current
x I
n
T at a given moment
%
Max. temp. rise allowed
degrees
Temp. rise at a given moment
degrees
Hot spot estimate
degrees
Hot spot maximum allowed
degrees
Trip delay rem.
seconds
Used SG
Setting group 1...8 active
5.3.10 Generator/transformer differential protection (Idb>/Idi>/I0dHV>/I0dLV>; 87T/
87N/87G)
The generator/transformer differential function is used for protecting the following power
transformers: two-winding transformers, and to some extent three-winding and two-winding
transformers that have double outputs and a summing application. This function can also be used for
protecting generators.
Figure. 5.3.10 - 49. Differential protection function can be used for protecting transformers, generators and both at the same
time.
A
AQ
Q-T256
-T256
Instruction manual
Version: 2.06
© Arcteq Relays Ltd
IM00028
103