Figure. 5.3.8 - 44. Simplified function block diagram of the transformer status monitoring function.
The function's outputs are dependent on the set transformer data because the measured currents (in
p.u.) are related to the transformer nominal values. The following diagram presents the function's
outputs in various situations.
Figure. 5.3.8 - 45. Activation of the function's outputs.
A
AQ
Q-T256
-T256
Instruction manual
Version: 2.06
© Arcteq Relays Ltd
IM00028
89