Figure. 5.5.1 - 222. Primary side high-impedance earth fault.
In this example there is a high-impedance earth fault. It does not activate the function, if the
measurement conditions are met, while the calculated and measured residual current difference does
not reach the limit. The
I
sum
difference setting should be set according to the application in order to
reach maximum security and maximum sensitivity for the network earthing.
Events and registers
The current transformer supervision function (abbreviated "CTS" in event block names) generates
events and registers from the status changes in ALARM ACTIVATED and BLOCKED signals. The user
can select which event messages are stored in the main event buffer: ON, OFF, or both.
The events triggered by the function are recorded with a time stamp and with process data values.
Table. 5.5.1 - 234. Event codes.
Event number
Event channel
Event block name
Event code
Description
3328
52
CTS1
0
Alarm ON
3329
52
CTS1
1
Alarm OFF
3330
52
CTS1
2
Block ON
3331
52
CTS1
3
Block OFF
The function registers its operation into the last twelve (12) time-stamped registers; this information is
available for all provided instances separately. The register of the function records the ON event
process data for ACTIVATED, BLOCKED, etc. The table below presents the structure of the function's
register content.
A
AQ
Q-M215
-M215
Instruction manual
Version: 2.04
355
Содержание AQ-M215
Страница 1: ...AQ M215 Motor protection IED Instruction manual ...
Страница 410: ...Figure 7 4 242 Example block scheme A AQ Q M215 M215 Instruction manual Version 2 04 409 ...
Страница 432: ...Figure 8 14 265 Panel cutout dimensions and device spacing A AQ Q M215 M215 Instruction manual Version 2 04 431 ...
Страница 466: ...10 Ordering information A AQ Q M215 M215 Instruction manual Version 2 04 465 ...